|   |  | 
ENGINE DIVISION SERVICE MANUAL
TM 5-4210-230-14&P-1
Fig.  71  Air Injection Pump With Diverter Valve
(Except California)
(1)
Disconnect   left   bank   air   injection   hose   from   air
manifold  check  valve  and  connect  air  pump  output
tester SE-2498 to end of hose.
(2)
Disconnect  left  bank  pressure  limiting  hose  from  air
cleaner and plug end of hose.
(3)
Connect tachometer to engine.
(4)
Operate   engine   at   speed   specified   (see   Emission
Control Tune-Up Specifications)
(5)
Observe pressure indicated.  If air pressure does not
exceed minimum specification (see Emission Control
Tune-Up  Specifications)  perform  the  following  steps
a, b, c and d.
a.
Check   air   hoses   for   leaks.     Check   diverter
valve  for,  external  leaks.    If  leaks  are  found,
replace   hose(s)   and/or   diameter   valve   and
repeat steps 4 and 5.
b.
Disconnect   air   hose   (connecting   air   pump
outlet   to   diverter   valve   inlet)   from   diverter
valve and connect air pump output tester SE-
2498 to end of hose.
c.
Operate    engine    at    specified    speed    (see
Emission 
Control 
System 
Tune-Up
Specifications) 
and 
observe 
minimum
pressure.
(1)
If  air  pressure  is  less  than  specified  minimum  (see
Emission  Control  System  Tune-Up  Specifications),
air  pump  is  faulty  and  must  be  replaced.    When
installing  a  new  air  pump  or  adjusting  the  air  pump
belt tension, do not pry on the pump housing.
(2)
If    air    pump    pressure    is    higher    than    specified
minimum   (see   Emission   Control   System   Tune-Up
Specifications),  diverter  valve  is  faulty  and  must  be
replaced.
d.
Connect air pump output tester SE-2498 to air
injection   hose   removed   from   check   valve.
Connect  air  injection  hose  from  air  pump  to
diverter valve inlet and repeat steps 4 and 5.
(6)
With    the    engine    operating    at    speed    specified,
observe   the   pressure   gauge.      Multiply   observed
pressure    by    .7    to    obtain    multiplied    pressure.
(Example:  Observed  pressure  is  6  PSI  and  multiply
by .7.  6 x .7 = 4.2 PSI multiplied pressure)
(7)
Remove   plug   in   the   pressure   limiting   hose   and
observe the pressure gauge.
a.
If  observed  pressure  in  step  7  is  higher  than
multiplied pressure in step 6, diverter valve is
acceptable for further use.
b.
If  observed  pressure  in  step  7  is  lower  than
multiplied pressure in step 6, diverter valve is
faulty and must be replaced.
(8)
With  the  engine  operating  at  speed  specified  (see
Emission  Control  System  Tune-Up  Specifications),
remove vacuum hose from diverter valve and check
for vacuum pull at the end of the hose.  If no vacuum
is felt, check for restriction in vacuum hose, vacuum
manifold  and  carburetor  vacuum  port.    Repair  as
needed.
CGES-215  Page 41
PRINTED IN UNITED STATES OF AMERICA
 
 |