2-13.
FIRE PUMP - Continued
2-13.7
Water Ring Primer - Continued
(40) Tighten setscrews (10) firmly, and lock into position with locknuts (11). Torque locknuts to 24 ft lb (33 Nm).
(41) Install and attach primer return spring.
(42) Install priming hose (2) and fasten to suction elbow (3) and priming valve (4) using gear clamps (1).
(43) Check adjustment of disengaging unit as detailed in para. 2-13.11.
(44) Test fire pump as detailed in para. 2-13.14.