TM 5-4210-220-34 2-13. FIRE PUMP - Continued 2-13.7 Water Ring Primer - Continued (16)  Carefully tap impeller end of primer shaft (19) until the primer shaft and bearings are clear of primer bearing housing (37).  Make sure to use a soft faced hammer. (17)  Inspect ball bearings (14 and 17) as detailed in para. 2-7. To prevent personal injury or premature bearing failure when removing or installing bearing races, always exert force on the tight ring of the bearing. (18)  Press bearings (14, 17) from primer shaft (19) if evidence of damage or wear is noticed. (19)  Push the seal (25) and back-up washer (24) towards the impeller cavity and remove from the bearing housing (37). (20)  Remove all gasket material or corrosion from all mating surfaces. (21)  Install  back-up  washer  (24),  and  primer  shaft  seal  (25)  into  primer  bearing  housing  (37)  from  the  impeller cavity  side.    Ensure  the  lip  on  the  back-up  washer  and  the  open  end  of  seal  face  are  mounted  toward  the impeller. To prevent personal injury or premature bearing failure when removing or installing bearing races, always exert force on the tight ring of the bearing. 2-106

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business