Page Title: EXCESS FOAM FROM TURRET OR NOZZLE
Back | Up | Next

Click here for a printable version

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Combat
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
USMC
   
Products
  Educational CD-ROM's
Printed Manuals
Downloadable Books
   

 

TM 5-4210-220-12 Table 3-1.  OPERATOR TROUBLESHOOTING - Continued MALFUNCTION TEST OR INSPECTION CORRECTIVE ACTION 6b  EXCESS FOAM FROM TURRET OR NOZZLE More than one foam proportioning valve open. Close foam proportioning valve on unmanned station. 7  ROOF OR BUMPER TURRET WILL NOT DISCHARGE Step 1.  Check manual valve in cab roof is open. Open manual valve. Step 2.  Check pump ON lamp is lit. Carry out correct operating procedure to start pump, (see para. 2-11). 8  FOAM ENTERING WATER TANK Check water tank valve is closed. Close valve. 9  WATER ENTERING FOAM TANK Check foam tank valve is closed. Close valve. 10a  WINTERIZATION HEATER NOT HEATING Step 1.  Check if heater switched ON. Set heater switch to ON, check indicator illuminates. Step 2.  Check battery switch in cab set to 1, 2, or BOTH. Set battery switch to 1, 2, or BOTH. Step 3.  Heater thermal breaker tripped by overheating. Reset thermal breaker, (see para. 2-12). 3-7

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business