Page Title: Table 2-2.. Nitrogen Pressure Regulator Temperature vs. Pressure Corrections
Back | Up | Next

Click here for a printable version

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Combat
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
USMC
   
Products
  Educational CD-ROM's
Printed Manuals
Downloadable Books
   

 

TM 5-4210-218-13&P NOTE The  steps  that  follow  are  to  recapture  the  Halon  leftover  in  the  pump  and  hoses back into the Halon supply cylinder. ab. After all fire extinguishers are processed, verify that the valve on the Halon hose is closed. ac. Close ball valve on nitrogen supply cylinder.  Loosen nitrogen pressure regulator from nitrogen cylinder and bleed off nitrogen. ad. Place the tilt rack in the upright position. ae. Place the unit operation valve in the recover position. af. Open the valve on the Halon hose. ag. Place the HALON/NITROGEN valve in the HALON position. ah. Start the pump by rotating the pump control valve 90 degrees counterclockwise to the ON position.  Operate the pump until the INLET PRESSURE gauge reads minus 5 psi vacuum. ai. Close valve on the Halon hose, stop the pump and close valves on Halon supply cylinder. aj. Return the UNIT OPERATION valve to the OFF position. ak. Return the HALON/NITROGEN valve to the OFF position. al. Stop the compressor. am. Remove the adapters from extinguisher hose and place adapters in tool box. an. Disconnect Halon hose from Halon cylinder and air compressor hose from air filter. ao. Stow hoses in approved manner. ap. If used, remove extinguisher support base from agitator bracket and place in tool box. 2-10.2  For the Bradley Infantry Fighting Vehicle (engine compartment).  (Refer to Figure 2-7) WARNING Sudden  release  of  compressed  gases  may  cause  severe  injury  to  personnel.    Do not deviate from approved procedures.  Wear safety goggles or face shield, gloves and   hearing   protection   when   working   with   pressurized   equipment.      Perform operating procedures in a well ventilated area. a. Connect the Bradley adapter, stored in tool box, to the nitrogen monitor adapter assembly.  The Bradley adapter is straight with a swivel fitting at one end. b. Start the air compressor.  Adjust the air inlet regulator on the Recovery / Recharger Unit to 140 psi (965 kPa). c. Attach extinguisher support base, P/N 12463589 (item 6, Appendix D) to agitator bracket. 2-25

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business