TM 10-4210-235-13
1-7 EQUIPMENT DATA.
Dimensions:
Fire Suppression Equipment Set
Length
149 in. (379 cm)
Width
76 m. (193 cm)
Height
75 m. (191 cm)
Auxiliary Cart
Length
48 in. (122 cm)
Width
45 in. (114 cm)
Height
59 in. (150 cm)
Weight:
Fire Suppression Equipment Set
Without Chemical Agents (Empty N2 Cylinders)
2960 lbs (1343 kg)
Fire Suppression Equipment Set Fully Serviced
4287 lbs (1945 kg)
Dry Chemical (Potassium Bicarbonate)
450 lbs (204 kg)
AFFF Concentrate (6%)
50 lbs (23 kg)
Water
783 lbs (355 kg)
Nitrogen (N2) Per Cylinder
22 lbs (10 kg)
Auxiliary Cart
455 lbs (206 kg)
Operating Pressure
Tanks and Hoses
220-240 psi (1518-1656 kPa)
Nitrogen (N2) Cylinder 1750 psi - 2400 psi (12075 kPa - 16560 kPa)
Capacities:
Dry Chemical (Potassium Bicarbonate)
450 lbs (204 kg)
AFFF Solution (6%)
100 gal (376 1)
Nitrogen (N2)
300 cu ft (85 cu m) per cyl
Heater Power Requirements
120/240 vac, 1 ph, 60 hz, 1300 w
Flow Rates:
AFFF (150 ft (46 m) hose)
51 gpm (192 Ipm)
AFFF (300 ft (91 m) hose)
40 gpm (150 Ipm)
Dry Chemical (150 ft (46 m) hose)
5.0 pps (2.3 kgps)
Dry Chemical (300 ft (91 m) hose)
4.4 pps (2.0 kgps)
Continuous Flow Time:
AFFF (150 ft (46 m) hose)
1 min., 58 sec
AFFF (300 ft (91 m) hose)
2 min., 30 sec
Dry Chemical (150 ft (46 m) hose)
1 min , 19 sec
Dry Chemical (300 ft (91 m) hose)
1 min., 42 sec
Operating Temperature Range (With AFFF Heater)
-40 F to +130 F (40 C to +54 C)
1-6
|