Quantcast Table 1. Operator Preventive Maintenance Checks and Services - continued - TM-55-1925-292-14-P0171

 

Click here to make tpub.com your Home Page

Page Title: Table 1. Operator Preventive Maintenance Checks and Services - continued
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

Share on Google+Share on FacebookShare on LinkedInShare on TwitterShare on DiggShare on Stumble Upon
Back
Table 1. Operator Preventive Maintenance Checks and Services - continued - TM-55-1925-292-14-P0170
Up
TM-55-1925-292-14-P Firefighting Fire Alarm and Fire Suppression Systems Inland and Coastal Large TUG (LT) Manual
Next
Table 2. Diesel Engine-Driven Firefighting Pump Oil
TM 55-1925-292-14&P
0012 00
Table 1. Operator Preventive Maintenance Checks and Services (continued)
ITEM INTERVAL
MAN-
ITEM TO BE
PROCEDURE
EQUIPMENT
NO.
HOUR
CHECKED OR
NOT READY/
SERVICED
AVAILABLE IF:
12
Quarterly
2.0
Pump
Service the diesel engine-driven fire-
fighting pump (WP 0015 00).
BREATHER
SIGHT GLASS
FIRE DETECTION
SYSTEM
13
Semiannual
0.2
Supervisory
Move the RESET/LAMP TEST switch
Any control
Circuits
to RESET. All visual indicators on the
panel does not
control panel should light and trouble
light, or trouble
horn should sound.
horn does not
sound.
14
Annual
4.0
Fire Hoses
Pressure test (FM 55-502).
Fire hose fails
pressure test.
0012 00-7

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc.
6230 Stone Rd, Unit Q Port Richey, FL 34668

Phone For Parts Inquiries: (727) 493-0744
Google +