RESET THE EDG ROOM FIRE FLAPS
TM 55-1925-292-14&P
0005 00
EMERGENCY DIESEL GENERATOR (EDG) ROOM FIRE FLAP OPERATION
DEPLOY THE EDG ROOM FIRE FLAPS
1. Ensure that all personnel are clear of the EDG room.
2. Secure the watertight door to the EDG room (figure 22, item 1).
3. Pull OUT on both T handles (figure 22, item 2) to deploy the EDG room fire flaps (figure 22, items 3 and 4).
4. Notify the pilothouse of the fire condition.
1
3
2
4
Figure 22. Emergency Diesel Generator (EDG) Room Fire Flap Operation
0005 00-23